Review Details: RESUBMITTAL

Permit Number - T05CM01943
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/29/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/05/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. "Electrical Power Plan does not appear to have a circuit for E15 Heavy Duty Table, which draws 10.1 A per the Equipment Schedule." THIS COMMENT WAS MADE ON THE FIRST SUBMITTAL. Response duly noted as "Deleted". Equipment E-15 has not been deleted. It resides center north on the Electrical Power Plan.
2. "Plot location of service entrance on scaled drawing. Plans Examiner to verify distance to new panel." THIS COMMENT WAS MADE ON THE FIRST SUBMITTAL. Response duly noted as "See Site plan." Could not tell exactly where existing service entrance is from Site plan.
3. "Provide service load calculations per NEC 220, or justify the use of 15VA/SF for HVAC and 10 VA/SF for restaurant equipment per this Article." THIS COMMENT WAS MADE ON THE FIRST SUBMITTAL. Response duly noted as "See panel schedule for loads calculation." Panel schedule does not provide service load calculation. Please review Article 100 for definitions relating to services and feeders.