Permit Number: T05CM01927
Parcel: 11520005P

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01927
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2005 JIM EGAN FIRE REVIEW Approved
05/02/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
05/03/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Complete the water isometric to include all of the added fixtures. Reference Section 103.2.3, UPC 1994.
2. Provide the applicable material standards for the fixtures being supplied by the owner. Reference Section 103.2.3, UPC 1994.
05/03/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) provide details and structual calculations justifying support of new AC unit.
2) provide clarification of seperated use. Provide wall section justifying speration between tenants.
3) Provide clearance for accessibility approach for getting out of toilet #2.
05/03/2005 ROBERT SHERRY WATER REVIEW Approved
05/03/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM01927 DENIED 5/2/05

1. Provide a circuit for receptacle by VM, on Power Plan.
2. On Ckt S-19, add the EF on the Power Plan, and add the load intended for the J-box drawn on the Lighting Plan.
3. It appears that the ceiling fans on Ckt S-1 should have demand factor 1.25, for continuous load.
4. Please justify the use of the demand factor of 0.7 for the power poles and hair dryers. May be diversity, but would like to discuss, because the loading is so close on this panel. 791.5550 x1106.
05/03/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations to include the common ventilation supply. reference Section 403.3.2, IMC 2000.
2. Provide a dryer vent. Reference Section 504.1, IMC 2000.
3. Show that the existing roof is capable of supporting the two new rooftop units. Reference Section 302.1, IMC 2000.
06/03/2005 GBONILL1 ZONING REVIEW Needs Review
06/03/2005 GBONILL1 WWM REVIEW Needs Review