Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01927
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/02/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
05/02/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
05/03/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Complete the water isometric to include all of the added fixtures. Reference Section 103.2.3, UPC 1994. 2. Provide the applicable material standards for the fixtures being supplied by the owner. Reference Section 103.2.3, UPC 1994. |
05/03/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) provide details and structual calculations justifying support of new AC unit. 2) provide clarification of seperated use. Provide wall section justifying speration between tenants. 3) Provide clearance for accessibility approach for getting out of toilet #2. |
05/03/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/03/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM01927 DENIED 5/2/05 1. Provide a circuit for receptacle by VM, on Power Plan. 2. On Ckt S-19, add the EF on the Power Plan, and add the load intended for the J-box drawn on the Lighting Plan. 3. It appears that the ceiling fans on Ckt S-1 should have demand factor 1.25, for continuous load. 4. Please justify the use of the demand factor of 0.7 for the power poles and hair dryers. May be diversity, but would like to discuss, because the loading is so close on this panel. 791.5550 x1106. |
05/03/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the ventilation calculations to include the common ventilation supply. reference Section 403.3.2, IMC 2000. 2. Provide a dryer vent. Reference Section 504.1, IMC 2000. 3. Show that the existing roof is capable of supporting the two new rooftop units. Reference Section 302.1, IMC 2000. |
06/03/2005 | GBONILL1 | ZONING | REVIEW | Needs Review | |
06/03/2005 | GBONILL1 | WWM | REVIEW | Needs Review |