Permit Review Detail
Review Status: Stopped
Review Details: COMMERCIAL TI
Permit Number - T05CM01925
Review Name: COMMERCIAL TI
Review Status: Stopped
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 05/02/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide information to show the fixtures being provided by the owner meet the plumbing material standards (P2, P3, P4, and the foot spas). 2. Clarify the nature of sink P4. 3. Revise the water fixture unit calculations to match the drawings. Revise the pipe sizing as required. |
| 05/02/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/02/2005 | ANY | WWM | REVIEW | Stopped | |
| 05/02/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 05/02/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/02/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM01925 DENIED 5/2/05 1. Specify voltage requirements for new WHs, on Plumbing Schedule. 2. Ckt B-6 should be 3000VA, not 1500VA. Also put the "*" by the description. 3. Provide feeder size for new Panels A and B. 4. If the new disconnects are being provided with this project, specify overcurrent protective devices. 5. Provide available fault current. 6. Provide fault calculations. 7. If this building was constructed after 1994, provide IECC calculations. |
| 05/02/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/17/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/02/2005 | ANY | APPROVAL SHELF | Stopped |
| 05/02/2005 | ANY | OUT TO CUSTOMER | Stopped |
| 05/02/2005 | ANY | REJECT SHELF | Stopped |