Permit Number: T05CM01902
Parcel: 14115008T

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01902
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2005 JIM EGAN FIRE REVIEW Approved
05/20/2005 DAVE MANN PLUMBING-COMMERCIAL REVIEW Passed
05/20/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
05/20/2005 DAVE MANN MECHANICAL-COMMERCIAL REVIEW Passed
05/20/2005 HEATHER THRALL ZONING REVIEW Approved
05/20/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
05/21/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied ELECTRICAL DENIED 5/21/05

1. Please demonstrate how 7 receptacles can be added with adding to electrical load. Indicate panel and circuit for each new receptacle, and provide an updated panel schedule, not just for existing.
05/26/2005 GERRY KOZIOL WWM REVIEW Approved
05/26/2005 ROBERT SHERRY WATER REVIEW Approved