Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM01902
Parcel: 14115008T

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01902
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Provide site plan with building location with set of permit documents with Architect of records stamp.
2) Provide code analysis data sheet.
3) Restroom facilities shall meet ansi 2003 standards A117.1 or justify per chapt. 34 IBC 20 % cost of construction has been spent towards meeting ANSI standards.
4) valuation needs to be provided to complete permit process.
05/06/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM01902 DENIED 5/6/05

Provide Panel schedule with load calculations.
05/20/2005 GBONILL1 PLUMBING-COMMERCIAL REVIEW Needs Review
05/20/2005 GBONILL1 FIRE REVIEW Needs Review
05/20/2005 GBONILL1 WWM REVIEW Needs Review
05/20/2005 GBONILL1 ZONING REVIEW Needs Review
05/20/2005 GBONILL1 MECHANICAL-COMMERCIAL REVIEW Needs Review
05/20/2005 GBONILL1 ENGINEERING REVIEW Needs Review
05/20/2005 GBONILL1 WATER REVIEW Needs Review