Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01884
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/28/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
04/28/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
04/28/2005 | ANY | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/28/2005 | JMORALE1 | WWM | REVIEW | Needs Review | |
04/28/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
04/28/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the ventilation calculations per Sections 403.3 and 403.3.2, IMC 2000. |
04/28/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM01884 DENIED 4/28/05 1. Please correct Ckt L1-11,24 on the Electrical Power Plan to read "L1-22,24." 2. Account for continuous loading on panel schedules. There is an "*" key for such, but it is not used. 3. Account for 25% for the largest motor on panel schedules. |
04/28/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/28/2005 | ANY | ENGINEERING | REVIEW | Approved |