Permit Number: T05CM01884
Parcel: 10714376G

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01884
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2005 JIM EGAN FIRE REVIEW Approved
04/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/28/2005 ANY BUILDING-COMMERCIAL REVIEW Approved
04/28/2005 JMORALE1 WWM REVIEW Needs Review
04/28/2005 TERRY STEVENS ZONING REVIEW Approved
04/28/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations per Sections 403.3 and 403.3.2, IMC 2000.
04/28/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM01884 DENIED 4/28/05

1. Please correct Ckt L1-11,24 on the Electrical Power Plan to read "L1-22,24."
2. Account for continuous loading on panel schedules. There is an "*" key for such, but it is not used.
3. Account for 25% for the largest motor on panel schedules.
04/28/2005 ROBERT SHERRY WATER REVIEW Approved
04/28/2005 ANY ENGINEERING REVIEW Approved