Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01883
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/28/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
04/28/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate the waste isometric with the floor plan. 2. Revise the fixture units per Tables 6-3 and 7-3, UPC 1994. 3. Finish noting the water pipe sizes on the water isometric. 4. Describe the sink. |
04/28/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM01883 DENIED 4/28/05 1. Per panel schedule Heat Pump FLA are 34A and 39A. Per Equipment Schedule Heat Pump FLA are 22A and 24.6A. Coordinate with Mechanical and clarify. 2. Per panel schedule Heat Pumps are connected single phase line-to-line. Clarify such on mechanical Equipment Schedule. 3. Per Plumbing Schedule WH is single phase 115V. Per electrical panel schedule this equipment takes 240V. Coordinate with Plumbing and clarify. (Plans Examiner will check panel schedule loading after the above comments are satisfied.) 4. Provide WH disconnect per NEC 422 Part III, or justify otherwise. 5. According to Riser Diagram, Panel A is existing in the all-in-one. Per the Electrical Plans there is a panel in the electrical room. Pls verify whether Panel A is new or existing, and its location. |
04/28/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/28/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
04/28/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The current code is the 2000 IMC, not the 1994 UMC. 2. Revise the exhaust fan controls to prevent recirculation of the air from the restrooms. |
04/28/2005 | ANY | ENGINEERING | REVIEW | Approved | |
05/09/2005 | KMEDINA1 | WWM | REVIEW | Needs Review | |
05/09/2005 | KMEDINA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/09/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |