Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T05CM01873
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 05/10/2005 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 05/16/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | S1. Provide seal and signature of structural engineer of record on drawings #16 and 17. S2. special Inspection required for : 1.Reinforcing. 2. Concrete. 3. Masonry. Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111. |
| 05/17/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/17/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 05/17/2005 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 05/19/2005 | DAVID RIVERA | ZONING | REVIEW | Denied | 05/19/05 Development Services Department Zoning Review Section David Rivera Principal Planner Comments: 1. The building plans have been reviewed by Zoning but the plans cannot be approved at this time. An approved and stamped site plan must is required prior to approval of the building plans. 2. Zoning will re-review the building plans on the next submittal to insure compliance with the approved site plan if the site plan is approved and stamped by all DSD reviewers. |
| 05/26/2005 | DOUG WILLIAMS | ENGINEERING | REVIEW | Denied | SUBJECT: Site Review - 3004 E. Wieding Rd.. DATE: 26 May 2005 ACTIVITY NUMBERS T05CM01873/T05OT01087 T15S, R14E, Section 8 Engineering Division has reviewed the Subject site plan and approval is not recommended at this time. Please provide a revised site plan addressing all comments provided. 1. Depict, label, and dimension any existing sidewalk, curb, or edge of pavement along the property frontage. If curbing exists, identify and label any existing curb cuts in the Right of Way, and provide notation on the plans that any unused curb cuts are to be closed (Chapter 25, Tucson Code). 2. If curbing exists, depict, label and dimension new FIVE (5)' wide sidewalk to be constructed in the Right of Way 2 feet (minimum) from the back of curb (DS 3-01.3.3 A). 3. Depict sidewalk scuppers where any site drainage may be concentrated, for conveyance of 10-year flows (min) under sidewalk areas, if applicable (DS 2-08.5.1 E & DS 3-01.4.4 F). 4. Depict and label sight visibility triangles (DS 2-02.2.1.10 & DS 3-01.5.B 2). 5. The proposed new electrical transformer does not appear to be within the property boundary - please clarify, and depict any easement with recording information, associated with this proposed item. If you have any questions, I can be reached at 791-5550, ext. 1189 or via email at Doug.williams@tucsonaz.gov. Douglas Williams Sr. Eng. Associate Engineering Division Development Services Department |
| 05/26/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Provide 15 KVA Transformer primary and secondary conductor size. Suggest this be done on the line diagram, and that motor runs be added here as well. 2. Provide for the grounding of this transformer as a derived system. Reference NEC 250.30 (A). 3. Please provide the size for the Grounding Electrode conductor at the service. 4. Provide for the grounding of the new panel at the Gas Engine Building as a Separate Building or Structure per NEC 250.32 (A) & (B) (1). 5. Show receptacles at Control Building. 8. All plans which include exterior lighting shall comply with the newly-adopted Lighting Ordinance, http://www.tucsonaz.gov/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/06/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |