Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM01833
Parcel: 13312006M

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01833
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2005 JIM EGAN FIRE REVIEW Approved
04/26/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/26/2005 ANY ENGINEERING REVIEW Approved
04/26/2005 ROBERT SHERRY WATER REVIEW Approved
04/26/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations to show that the tenant spaces receive adequate ventilation. Reference Section 403, IMC 2000.
2. Provide smoke detectors for rooftop units supplyiong over 2000 CFM.
04/27/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TO5CM01833 DENIED 4/26/05

Ckts WB-21, WB-19, and WB-9 have lighting loads per Sheet E2. Please account for them on panel schedule. Then Plans Examiner will check panel loading.
05/06/2005 JMORALE1 WWM REVIEW Passed
05/06/2005 JMORALE1 ZONING REVIEW Needs Review
05/06/2005 JMORALE1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/06/2005 JMORALE1 OUT TO CUSTOMER Completed