Permit Number: T05CM01790
Parcel: 11454008B

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T05CM01790
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2005 PAUL MACHADO ENGINEERING REVIEW Denied The Flood Plain use permit must be approved prior to the issuance of the building permit.
05/20/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: VC1 Construction Co., Inc. DATE: May 20, 2005
6404 E. Tanque Verde Rd.
Tucson, Arizona 85715

SUBJECT: 8770 E. Bears Path Road
Site plan T05CM01790 (First Review)
T13S, R15E, Section 34

RESUBMITTAL REQUIRED: Site Plan and Hydrology Report.

The Site Plan (SP), Hydrology Report and Floodplain Use Permit (FUP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Building Permit:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. A Site plan is required for this project.
3. Show the 100-year floodplain and water surface elevation per D.S. 2-02.2.1.15.
4. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
5. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17. A grading plan will be required.
6. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
7. Placement of fill in excess of 2' above existing grade at any location in the outer 100' of the developing site is not allowed and/or shall meet the requirements per D.S. 11-01.
8. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
9. List the consulting engineer and the owner/developer on the plans with the pertinent information.
10. Add note: "Depress all landscaped areas 6" maximum for water harvesting".

Hydrology Report:
1. Please include a response letter to the comments along with the corrected copies of the HR.
2. The WSEL for the Tanque Verde from the FIRM panel is listed in DR as being 2524. The WSEL for the Tanque Verde wash should be interpolated at the highest end of the proposed residence. Therefore, an interpolation of 2526.5 shall be used to calculate the "Lowest floor elevation". See attached sheet.
3. Placement of fill in excess of 2' above existing grade at any location in the outer 100' of the developing site is not allowed and/or shall meet the requirements per D.S. 11-01.

Floodplain Use Permit:
1. The FUP cannot be issued prior to the approval of the SP.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/8770 E. Bears Path Rd
05/23/2005 GERRY KOZIOL WWM REVIEW Approved
05/23/2005 LINHART PETERSEN POWERS ASSOC BUILDING-RESIDENTIAL REVIEW Completed Comments to be entered when received from reviewer.