Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01768
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 04/21/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/21/2005 | ANY | BUILDING-COMMERCIAL | REVIEW | Denied | S1. ADDRESS ACCESSIBILITY. S2. CLARIFY SAFETY GLAZING AT SIDELITE. |
| 04/21/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/21/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 04/21/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/21/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/21/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 04/25/2005 | JMORALE1 | WWM | REVIEW | Passed |