Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM01726
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM01726
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The submitted structural calculations did not include the weight of a person working on the hood as required by Section 507.6, IMC 2000.
08/17/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/18/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE DETAIL FOR KITCHEN HOOD INSTALLATION - SHOULD BE A PART OF THE PERMIT SET DRAWINGS. PROVIDE ROOF FRAMING PLAN / PLAN VIEW AND CONNECTION DETAIL.
09/06/2005 STANTEC ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/06/2005 KMEDINA1 OUT TO CUSTOMER Completed