Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM01723
Parcel: 137084560

Review Status: Completed

Review Details: PLANS OK TO SUBMIT - COMM

Permit Number - T05CM01723
Review Name: PLANS OK TO SUBMIT - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2005 MICHAEL ST. PAUL ZONING REVIEW Passed
04/20/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/03/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approved
06/03/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM01723 DENIED 4/20/05

GND in run between transformer and first disconnect shall be sized per the derived conductors. Please change to #4 per NEC Table 250.66.