Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2005 MICHAEL ST. PAUL ZONING REVIEW Passed
04/20/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
06/03/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approved
06/03/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM01723 DENIED 4/20/05

GND in run between transformer and first disconnect shall be sized per the derived conductors. Please change to #4 per NEC Table 250.66.