Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM01719
Parcel: 13216600B

Address:
4220 S PARK AV

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM01719
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
05/06/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM01719 DENIED 5/2/05

1. Chiller Schedule Sheet M2 calls for MOCP 175. The 200A circuit breakers at the control panel and MCC-1 are above this maximum.
2. Now that MCC-1 has been located on the electrical plans, it is obvious that the disconnect is not within sight of the controller location. Reference NEC 430.102 (A). Reword Keynote #1.
3. Demonstrate that the maintenance receptacle is not connected to the load side of the disconnecting means. Reference NEC 210.63.