Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/02/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
05/06/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM01719 DENIED 5/2/05 1. Chiller Schedule Sheet M2 calls for MOCP 175. The 200A circuit breakers at the control panel and MCC-1 are above this maximum. 2. Now that MCC-1 has been located on the electrical plans, it is obvious that the disconnect is not within sight of the controller location. Reference NEC 430.102 (A). Reword Keynote #1. 3. Demonstrate that the maintenance receptacle is not connected to the load side of the disconnecting means. Reference NEC 210.63. |