Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01714
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide valuation for building seperate suite. 2) Restroom needs to meet ANSI 117.1 2003 standards. Show Clear floor space required for water closet or provide breakdown that 20 % cost of construction is being spent towards meeting accessibility requirements per chapt. 34. |
| 04/19/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/19/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TO5CM01714/5 DENIED 4/19/05 1. Provide identification of #120 and #130 on plans. 2. Provide documentation of all electrical devices and systems which pertain to these two suites. |
| 04/19/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/19/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the ventilation of the space complies with the requirements of Section 403.3, IMC 2000. 2. Provide information to show that the HVAC for the suite serves only this suite. |
| 05/27/2005 | JMORALE1 | FIRE | REVIEW | Needs Review | |
| 05/27/2005 | JMORALE1 | WWM | REVIEW | Needs Review | |
| 05/27/2005 | JMORALE1 | ZONING | REVIEW | Needs Review | |
| 05/27/2005 | JMORALE1 | ENGINEERING | REVIEW | Needs Review |