Permit Number: T05CM01712
Parcel: 12302089A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01712
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Provide valuation for cost to create individual suites.
2) Dimension corridor for accessibility to restroom.
04/19/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/19/2005 ROBERT SHERRY WATER REVIEW Approved
04/19/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the ventilation of the space complies with the requirements of Section 403.3, IMC 2000.
2. Provide information to show that the HVAC for the suite serves only this suite.
05/27/2005 JMORALE1 FIRE REVIEW Needs Review
05/27/2005 JMORALE1 WWM REVIEW Needs Review
05/27/2005 JMORALE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review TO5CM01714/5 DENIED 4/19/05

1. Provide identification of #120 and #130 on plans.
2. Provide documentation of all electrical devices and systems which pertain to these two suites.
05/27/2005 JMORALE1 ZONING REVIEW Needs Review
05/27/2005 JMORALE1 ENGINEERING REVIEW Needs Review