Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01712
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) Provide valuation for cost to create individual suites. 2) Dimension corridor for accessibility to restroom. |
| 04/19/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/19/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/19/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the ventilation of the space complies with the requirements of Section 403.3, IMC 2000. 2. Provide information to show that the HVAC for the suite serves only this suite. |
| 05/27/2005 | JMORALE1 | FIRE | REVIEW | Needs Review | |
| 05/27/2005 | JMORALE1 | WWM | REVIEW | Needs Review | |
| 05/27/2005 | JMORALE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | TO5CM01714/5 DENIED 4/19/05 1. Provide identification of #120 and #130 on plans. 2. Provide documentation of all electrical devices and systems which pertain to these two suites. |
| 05/27/2005 | JMORALE1 | ZONING | REVIEW | Needs Review | |
| 05/27/2005 | JMORALE1 | ENGINEERING | REVIEW | Needs Review |