Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM01710
Parcel: 141185820

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM01710
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM01710 DENIED 4/22/05
1. Provide disconnect for new WH, or justify otherwise.
2. Provide 2000 IECC calculations for Lighting Power Budget.
3. Provide Panel S1 loading in amps.
4. Provide load calculation for entire service.
04/22/2005 DAVE MANN MECHANICAL-COMMERCIAL REVIEW Approved
04/22/2005 DAVE MANN PLUMBING-COMMERCIAL REVIEW Approved
04/26/2005 KMEDINA1 WWM REVIEW Needs Review
04/26/2005 KMEDINA1 BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/26/2005 KMEDINA1 OUT TO CUSTOMER Completed