Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01710
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 04/19/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plumbing plans showing how the existing lavatory is to be moved and how the new sink is to be installed. 2. The minimum size for the waste from a commercial bar sink is 2". 3. Provide cleanouts per Section 707.4, UPC 1994. |
| 04/19/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE VALUATION FOR T.I. 2) COMPLETE CODE ANALYSIS SEPERATED USE? NONSEPERATED USE? CLARIFY OCCUPANCY NEXT TO SUITE. JUSTIFY ALLOWABLE SQUARE FOOTAGE. 3) MINIMUM TEXT SIZE = 10 PT PROVIDE NEW DOCUMENTS 4) CLARIFY LOCK SET FOR EXITING PURPOSES. 5) CLARIFY CONNECTORS FOR MTL STUD FRAMING ATTACHMENT TO EXISTING STRUCTURE. |
| 04/19/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/19/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 04/19/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information to show that the existing exhaust fan in the restroom complies with the flow requirements of Section 403.3, IMC 2000. 2. Provide a sequence of operation for the restroom exhaust to show that there will be no recirculation of air from the restroom. |
| 04/19/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 04/19/2005 | DOUG WILLIAMS | ENGINEERING | REVIEW | Approved | |
| 04/22/2005 | DROBEY1 | WWM | REVIEW | Needs Review |