Permit Number: T05CM01706
Parcel: 118021100

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T05CM01706
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2005 GERRY KOZIOL WWM REVIEW Denied needs to identify plumbing fixtures stubbed out for
05/16/2005 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS for Activity # T05CM01706

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, model energy and electrical. All code references are to the 2003 International Residential Code, 2000 International Energy Conservation Code, and Arizona State Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

All dimensions and notes shall be consistent on each plan or elevation.
1. Clarify "Compact ABC fill" note on Detail #3, sheet A4.
2. Clarify the footing note at the top plate on Detail #6, sheet A6.

FOUNDATION PLANS:

1. Note on the drawings the allowable soil bearing pressure used in the design of the footings, or state that the assumed value of 1500 PSF is being used per table R401.4.1 if this does not conflict with the designer / homebuilder's awareness of the soil and conditions of the site. If soil testing is being done, note that a copy of the soils report shall be submitted with the construction plans, and the foundation design shall reflect the soils reports recommendations.
2. Note that grade away from foundations shall comply with R401.3.

FLOOR PLANS:

1. Show compliance with R303.1 providing natural light (8%) and natural ventilation (4%) into the Office/Den.

STRUCTURAL PLANS:

1. Provide manufacturer's calculations and data for pre-fabricated trusses and glue-lam beams, or note the requirement for deferred submittal at installation. Truss calculations must be signed, dated and wet-sealed by an engineer who is registered in Arizona. Truss calculations shall be cross-referenced to the floor plans. The engineer of record shall review and "SHOP DRAWING" stamp approval on truss calculations.

ELEVATIONS:

1. Show calculation of attic ventilation area in compliance with R806.2. Note size and location of all vents needed to comply.

PLUMBING PLANS:

1. Note and specify all work to be performed. V.T.R. and C.O. appear in the new construction plan without notation. Label for future bathroom if appropriate.
2. Hose bibs may be calculated at 3 fixture units each.
3. The City of Tucson has adopted the 1994 Uniform Plumbing Code with state amendments (ARIZONA STATE PLUMBING CODE). All plans must reference this code.

MECHANICAL PLANS:

1. Note on plans: Mechanical shall comply with 2003 IRC chapters 13 - 24.
2. Clarify the Mechanical Spec's note for the location and details of the new 5 ton A/C.

ELECTRICAL PLANS:

1. Note on plan that all electrical work shall comply with 2003 IRC chapters 33 - 42. Correct Electrical Notes #1, 2, 3, 6, 7, 8 and 10 and the Riser Diagram.
2. Provide an exterior outlet at grade level located at both the front and back of the dwelling or show location of existing, per E3801.7. These outlets shall be GFCI protected per E3802.3.
3. Indicate the location of all air conditioning and heating units, air handlers, compressors, and disconnects.
4. Provide a note indicating only approved outlet boxes shall be used for ceiling fans, per E4001.6.
5. Show breaker sizes on new 100 amp sub-panel. Show circuit number on receptacle in future storage room/bathroom.

If you have any questions, please contact your assigned plans examiner Ken Van Karsen at 791-5550, extension 1112.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/27/2005 DELMA ROBEY OUT TO CUSTOMER Completed