Permit Review Detail
Review Status: Stopped
Review Details: OTHER
Permit Number - T05CM01661
Review Name: OTHER
Review Status: Stopped
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/15/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 04/15/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 05/04/2005 | ANY | WWM | REVIEW | Stopped | |
| 05/04/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show the location of the cleanouts for the building sewers (gravity flow to the sump). 2. Show the slopes of the building sewers. |
| 05/04/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM01661 DENIED 5/4/05 1. It appears that electrical has been pencilled in. Registrant shall annotate this as a revision to the sealed plans so that Plans Examiner may verify that such electrical was done by the Engineer. 2. Two sets are required for Over-the-Counter service. 3. Locate pump disconnect on plans, Reference NEC 430 Part IV. 4. Locate panel on plans. 5. Provide panel and circuit number for motor circuit. 6. Provide panel voltage and load capacity. 7. Demonstrate that panel is not overloaded. 1/2 HP motor draws 9.8 A per NEC Table 430.148. 2. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/14/2005 | ANY | APPROVAL SHELF | Stopped |
| 04/14/2005 | ANY | OUT TO CUSTOMER | Stopped |
| 04/14/2005 | ANY | REJECT SHELF | Stopped |