Permit Number: T05CM01661
Parcel: 14020009C

Address:
5060 S PARK AV

Review Status: Stopped

Review Details: OTHER

Permit Number - T05CM01661
Review Name: OTHER
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/15/2005 TERRY STEVENS ZONING REVIEW Approved
05/04/2005 ANY WWM REVIEW Stopped
05/04/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the location of the cleanouts for the building sewers (gravity flow to the sump).
2. Show the slopes of the building sewers.
05/04/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM01661 DENIED 5/4/05

1. It appears that electrical has been pencilled in. Registrant shall annotate this as a revision to the sealed plans so that Plans Examiner may verify that such electrical was done by the Engineer.
2. Two sets are required for Over-the-Counter service.
3. Locate pump disconnect on plans, Reference NEC 430 Part IV.
4. Locate panel on plans.
5. Provide panel and circuit number for motor circuit.
6. Provide panel voltage and load capacity.
7. Demonstrate that panel is not overloaded. 1/2 HP motor draws 9.8 A per NEC Table 430.148.