Permit Number: T05CM01647
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01647
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2005 JIM EGAN FIRE REVIEW Approved
04/14/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/14/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a complete mechanical plan for the exhaust hood. A review of manufacturer's cut sheets is not acceptable.
1. Provide information to show how the existing fan is capable of supporting the new exhaust flowrate.
2. Revise the electrical to the fan as required.
3. Provide information to show how the existing makeup air system is to be modified to support the new requirements.
4. Provide details to show how the new hood is to be supported from the existing structure.
5. Show the design features and air balancing information for the new hood on the drawing.
6. Provide information to show that the existing exhaust duct is capable of accomodating the new exhaust flow.
04/14/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CLARIFY / JUSTIFY LOADS FOR EXISTING STRUCTURE AND DETAIL STRUCTURAL SUPPORT.
04/14/2005 ROBERT SHERRY WATER REVIEW Approved
05/06/2005 KMEDINA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
05/06/2005 KMEDINA1 WWM REVIEW Needs Review
05/06/2005 KMEDINA1 ZONING REVIEW Needs Review
05/06/2005 KMEDINA1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/06/2005 KMEDINA1 OUT TO CUSTOMER Completed