Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01647
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/14/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 04/14/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/14/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide a complete mechanical plan for the exhaust hood. A review of manufacturer's cut sheets is not acceptable. 1. Provide information to show how the existing fan is capable of supporting the new exhaust flowrate. 2. Revise the electrical to the fan as required. 3. Provide information to show how the existing makeup air system is to be modified to support the new requirements. 4. Provide details to show how the new hood is to be supported from the existing structure. 5. Show the design features and air balancing information for the new hood on the drawing. 6. Provide information to show that the existing exhaust duct is capable of accomodating the new exhaust flow. |
| 04/14/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | CLARIFY / JUSTIFY LOADS FOR EXISTING STRUCTURE AND DETAIL STRUCTURAL SUPPORT. |
| 04/14/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/06/2005 | KMEDINA1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 05/06/2005 | KMEDINA1 | WWM | REVIEW | Needs Review | |
| 05/06/2005 | KMEDINA1 | ZONING | REVIEW | Needs Review | |
| 05/06/2005 | KMEDINA1 | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/06/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |