Permit Number: T05CM01613
Parcel: 126162340

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T05CM01613
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2005 GERRY KOZIOL WWM REVIEW Approved
05/11/2005 NEAL SAUNDERS BUILDING-RESIDENTIAL REVIEW Denied Plan Check Comments - Project T05cm01613

Plan Review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

General Requirements

1. All corrections and revisions shall be made on the original tracings and two new sets of prints or (1) sepia and (1) blue line shall be returned.
2. Pencil corrections on final prints will not be acceptable. To avoid delays ensure that corrections have been made, are complete and have been coordinated on all-applicable details and notes.

Floor Plan

1. Callout size and operable portion of bedroom #1 window. Egress issue pending. Reference R310.
2. Windows 3, 4 and 7 need to be tempered per R308.4.
3. Window 6 may need to be tempered per R308.4 (#7).
4. Window 5 may need to be tempered per R308.4 (#6).

Foundation Plan

1. Indicate the slope for all exterior slabs, per R401.3.
2. Show locations of tiedowns on foundation plan.

Structural Plan

1. 9/A-2 and 6/A-2 - Note minimum lap of rebar from foundation into wall.
2. 8/A-2 - Note veneer ties around post.
3. 3/A-2 (sim) at new porch? Clarify.
4. Size minimum openings of 22" by 30" for over-framed areas.
5. 3/A-3 and 15/A-3 - Provide cross-bracing at gable end per R802.10.3.
6. Specify connection of all new posts to sill plate.
7. Specify new post connection to foundations at new dining room opening.
8. 2/A-3 and 8/A-3 - How will bird boards be effective ventilation with roof diaphragm blocking over plate.
9. Show calculation of attic ventilation area in compliance with R806.2. Note location of all vents needed to comply.
10. Provide minimum braced wall on wall behind master bath wall. Minimum panel of 2'-8" with tiedowns or 4" panel per R602.10. Panel must begin no less than 12' from end of building.
11. Specify nailing of interior braced wall in master bedroom.

Plumbing, Mechanical and Electrical Plan

1. Note on plan compliance with the water conservation requirements. Water closets, 1.6 gallons per flush, sinks and showerheads, 3 gallons per minute.
2. Note on plans that shower and tub / shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type.
3. Note on plans: Mechanical shall comply with 2003 IRC chapters 13 - 24.
4. Provide arc-fault protection for all bedrooms per E3802.11.
5. Show locations of smoke detectors per R313. Note that all smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are removed in existing construction, existing bedrooms shall be in compliance. When ceiling finish materials are not removed, existing bedrooms shall be equipped with battery operated smoke detectors per R313.1.1.
6. Circuit A-6 is for bathroom only per E3603.4. (see ext. GFI and closet recep).

MODEL ENERGY CODE:

1. Misprint on MEC callout R-9 (walls) should be R-19.

If you have any questions, please contact your assigned plans examiner Neil Saunders at 791-5550, extension 1113.

NOTE: As of 09/06/04 the City of Tucson has adopted the 2003 IRC with the exception of the plumbing portion which has been replaced with the Arizona state plumbing code. All model plans shall reference these codes.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/13/2005 JMORALE1 OUT TO CUSTOMER Completed
05/13/2005 SUE REEVES REJECT SHELF Completed