Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01602
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/12/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 04/14/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/14/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) CLARIFY / JUSTIFY SEPERATED / NON-SEPERATED USE. 2) RESTROOM FACILITIES MUST MEET ANSI A117.1 STANDARDS 2003 OR CLARIFY PER CHAPT. 34 20 % COST OF CONSTRUCTION IS BEING SPENT TOWARDS ACCESSIBILITY REQUIREMENTS. PROVIDE A BREAKDOWN. 3) CLARIFY / JUSTIFY DOOR ENCROACHMENT PER SECTION 1005.2 DOOR # 101 & 102. 4) CLARIFY / JUSTIFY DOOR INTO RESTROOM CORRIDOR MEETS ANSI STANDARDS A117.1 SECTION 404 DOORS AND DOORWAYS. |
| 04/14/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/14/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 04/14/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information to show how the provided ventilation rate complies with the requirements of Section 403.3, IMC 2000. 2. Show the size, route, and termination of the condensate drain from HP-2. Reference Section 106.3.1, IMC 2000. 3. Revise the duct insulation to comply with the requirements of Section 803.2.8, IECC 2000. |
| 04/14/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM01602 DENIED 4/14/05 1. City does not allow Up-0ver-Down method of attenuating fault current. Provide location of service on scaled drawing, and demonstrate by fault calculations that panel rating is not exceed for AFC. 2. Please check for available fault current at service. 32600A AFC as published by TEP applies to 277/480V services. 120/208V AFC is 75100A. |
| 05/17/2005 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 05/17/2005 | GBONILL1 | ZONING | REVIEW | Needs Review |