Permit Number: T05CM01602
Parcel: 11205283F

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01602
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/12/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
04/14/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/14/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY / JUSTIFY SEPERATED / NON-SEPERATED USE.
2) RESTROOM FACILITIES MUST MEET ANSI A117.1 STANDARDS 2003 OR CLARIFY PER CHAPT. 34 20 % COST OF CONSTRUCTION IS BEING SPENT TOWARDS ACCESSIBILITY REQUIREMENTS. PROVIDE A BREAKDOWN.
3) CLARIFY / JUSTIFY DOOR ENCROACHMENT PER SECTION 1005.2 DOOR # 101 & 102.
4) CLARIFY / JUSTIFY DOOR INTO RESTROOM CORRIDOR MEETS ANSI STANDARDS A117.1 SECTION 404 DOORS AND DOORWAYS.
04/14/2005 ROBERT SHERRY WATER REVIEW Approved
04/14/2005 JIM EGAN FIRE REVIEW Approved
04/14/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information to show how the provided ventilation rate complies with the requirements of Section 403.3, IMC 2000.
2. Show the size, route, and termination of the condensate drain from HP-2. Reference Section 106.3.1, IMC 2000.
3. Revise the duct insulation to comply with the requirements of Section 803.2.8, IECC 2000.
04/14/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM01602 DENIED 4/14/05
1. City does not allow Up-0ver-Down method of attenuating fault current. Provide location of service on scaled drawing, and demonstrate by fault calculations that panel rating is not exceed for AFC.
2. Please check for available fault current at service. 32600A AFC as published by TEP applies to 277/480V services. 120/208V AFC is 75100A.