Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T05CM01598
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/25/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/20/2005 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Approved | PLAN CHECK COMMENTS - PROJECT #T05CM01598 5/20/05 4218 E. WAVERLY ST. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2003 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. SITE PLAN: 1. INDICATE THE LOCATION OF THE WATER METER AND THE WATER SERVICE LINE. FLOOR PLANS: 1. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY ACCESSIBLE SPACE PER R807. 2. NOTE THAT THE SHOWER ENCLOSURE SHALL BE FINISHED PER p2710 WITH CERAMIC TILE, OR A LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2 3. NOTE AND SPECIFY THAT SHOWER ENCLOSURES SHALL HAVE A MINIMUM FINISHED INTERIOR OF 1,024 SQUARE INCHES AND SHALL BE CAPABLE OF ENCOMPASSING A MINIMUM 30" CIRCLE PER UPC SEC. 410.0. ALL GLASS ENCLOSURES SHALL BE TEMPERED. 4. SHOW THAT EACH WATER CLOSET IS LOCATED IN A CLEAR SPACE NOT LESS THAN 30" WIDE AND HAS A CLEAR SPACE IN FRONT OF NOT LESS THAN 24". STRUCTURAL PLANS: 1. PROVIDE THE HEADERS. 2. SPECIFY LUMBER GRADE AND SPECIES. 3. SPECIFY AND DETAIL ALL OVER FRAMING. IF SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREAS (>30 S.F.). IF SOLID SHEATHING IS NOT USED ON LOWER TRUSSES, PROVIDE DETAILS FOR BRACING OF TOP CHORD OF LOWER TRUSSES. ELEVATIONS: 1. INDICATE THE ROOF SLOPE. SECTIONS - DETAILS - MISC. NOTES: 1. S-2 / 1 ; PLEASE SPECIFY THE ANCHOR BOLT SPACING. 2. PROVIDE A RIDGE BOARD. 3. R-30 DOESN'T FIT IN A 2X6 CEILING. PLUMBING PLANS: 1. THE VENTING ISN'T IN ACCORD WITH THE '94 UPC. ELIMINATE THE FLAT VENT AND VENT THE SHOWER AND THE WATER CLOSET. IF YOU WANT TO USE THE INTERNATIONAL PLUMBING, AN APPROVED APPEAL TO THE BUILDING OFFICIAL IS REQUIRED. 2. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH FOR THE EXISTING AND THE PROPOSED IN ORDER TO CHECK THE EXISTING WATER SERVICE'S ADEQUACY TO SERVE THE EXISTING AND THE PROPOSED F.U.s . 3. PROVIDE THE SOURCE OF THE GAS LINE. IF IT TAPS AN EXISTING LINE, JUSTIFY THAT LINE'S ABILITY TO SERVE THE EXISTING AND THE PROPOSED DEMANDS. BACK TO THE METER? MECHANICAL PLANS: 1. SIZE THE SUPPLY AND RETURN AIR DUCTS. SEE M1403 . ELECTRICAL PLANS: 1. PLEASE ADD A NOTE, THAT THE LIGHT FIXTURE IN THE SHOWER IS REQUIRED TO BE LISTED AS APPROVED FOR USE IN WET AREAS. 2. PROVIDE A RECEPTACLE FOR THE BACK YARD USE IF ONE DOESN'T EXIST. PLEASE SEE E3801.7 . 3. PROVIDE A SMOKE DETECTOR IN THE MUD ROOM. SEE R313.1 ITEM 2 AND R313.1.1 FOR THE REQUIREMENT TO PROVIDE SMOKE DETECTORS FOR THE EXISTING HOUSE. 4. AT LEAST ONE WALL SWITCH CONTROLLED LIGHT OR OUTLET MUST BE PROVIDED IN BATHROOMS, HALLWAYS, STAIRWAYS, ATTACHED GARAGES, OUTDOOR ENTRANCES OR EXITS AND ALL HABITABLE ROOMS PER E3801. 5. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED OUTLET BOXES SHALL BE USED, PER E4001.6. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 791-5550 EXT. 1110 |