Permit Number: T05CM01590
Parcel: 13315320C

Address:
2130 N KOLB RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T05CM01590
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM01590 8/30/06

1. Provide grounding electrody system at canopy structure. Reference NEC 250.32.
2. Depth of cover is inadequate per NEC Table 300.5.
3. Provide catalogue cut sheet for disconnecting equipment and overcurrent protective devices.
4. There are still certain deficiencies upon third review. Suggest that this design be taken to an Electrical Engineer.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2006 GERARDO BONILLA OUT TO CUSTOMER Completed