Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T05CM01590
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM01590 8/30/06 1. Provide grounding electrody system at canopy structure. Reference NEC 250.32. 2. Depth of cover is inadequate per NEC Table 300.5. 3. Provide catalogue cut sheet for disconnecting equipment and overcurrent protective devices. 4. There are still certain deficiencies upon third review. Suggest that this design be taken to an Electrical Engineer. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/31/2006 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |