Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t05cm01590 8/29/06

1. Provide grounding electrode system at canopy structure. Reference NEC 250.32. Indicate whether Equipment Grounding Conductor will be in the conduit run to the canopy.
2. Provide conduit size, type, and depth of cover.
3. Total connected load is not obtained by adding Phases A and B. 96.1 A is load on Phase A and 75.1 A is load on Phase B.