| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/29/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t05cm01590 8/29/06 1. Provide grounding electrode system at canopy structure. Reference NEC 250.32. Indicate whether Equipment Grounding Conductor will be in the conduit run to the canopy. 2. Provide conduit size, type, and depth of cover. 3. Total connected load is not obtained by adding Phases A and B. 96.1 A is load on Phase A and 75.1 A is load on Phase B. |