Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL BLDG/WWM
Permit Number - T05CM01584
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/18/2005 | DAVE MANN | BUILDING-RESIDENTIAL | REVIEW | Approved | Sheet A1 1. If the bathroom 2 and master bedroom doors are locked there is no exit from the room between them. 2. The new smaller window sizes in bedrooms 1 and two do not appear to meet the minimum size for egress. Sheet A3 1. The roof vent location shown will not work with the insulation location shown. Sheet A4 1. Trusses 24 "oc require sag resistant or 5/8" gyp board. Sheet D1 1. A one inch air space is required under porch columns. Sheet M1 1. The gas line cannot run under the porch. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/23/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |