Permit Number: T05CM01580
Parcel: 13321158E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01580
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2005 JIM EGAN FIRE REVIEW Approved
04/11/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/11/2005 ROBERT SHERRY WATER REVIEW Approved
04/11/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
04/14/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
04/14/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
04/14/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/18/2005 GERRY KOZIOL WWM REVIEW Passed
04/18/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM01580 DENIED 4/14/05
1. Account for new receptacle load Panel Schedule Ckt 12.
2. Please re-calculate Phase A. See marks on plans.
3. Panel Schedule has main fuses. Line Diagram calls for Main CB. Please clarify.
4. Line Diagram calls for 50A CB on Panel. All phases would be overloaded with this CB.
5. Panel Schedule calls for 120/240V Panel. However, it is set up as a 120/208V. Please clarify.