Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01580
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/11/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 04/11/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/11/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 04/11/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 04/14/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/14/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 04/14/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 04/18/2005 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 04/18/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM01580 DENIED 4/14/05 1. Account for new receptacle load Panel Schedule Ckt 12. 2. Please re-calculate Phase A. See marks on plans. 3. Panel Schedule has main fuses. Line Diagram calls for Main CB. Please clarify. 4. Line Diagram calls for 50A CB on Panel. All phases would be overloaded with this CB. 5. Panel Schedule calls for 120/240V Panel. However, it is set up as a 120/208V. Please clarify. |