Permit Number: T05CM01577
Parcel: 125020720

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T05CM01577
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2005 GERRY KOZIOL WWM REVIEW Approved
05/24/2005 DAVE MANN BUILDING-RESIDENTIAL REVIEW Denied Identify on the window and door schedules the U-values and SHGC values and the opening size of the bedroom awning window.

Sheets A6.2 and S2.1, Dimension the footing width per IRC R403 and 404.

Sheet S2.2 The code used by Tucson is the 2003 IRC and the bearing value at the depth shown is 1000 psf.

Sheet A4.1 the rafters shown do not meet R802 with the tie loctions shown.

A4.2 All sill plates shal be treated or otherwise meet IRC R403.
05/24/2005 DAVE MANN BUILDING-RESIDENTIAL REVIEW Denied Sheet E1.1
Provide load calculations and show where the panel is fed from. Show a panel schedule, is AC 220 v?

Kitchen circuits need to be 20 amp.

Sheets P1.1 and 1.2 Please provide isometrics. The current drawnings are impossible to follow.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/27/2005 DELMA ROBEY OUT TO CUSTOMER Completed