Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T05CM01574
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/28/2005 | JIM EGAN | FIRE | REVIEW | Denied | 1. Fire hydrants required. Submit approved COT Water Plan. 2. Minimum 20 feet wide, PAVED, fire apparatus access roadway must be provided and extended to within 150 feet of all portions of the structure. |
| 05/16/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | DATE: May 16, 2005 TO: John Holley, WLB Group SUBJECT: Site Plan: NRM Tie Rehab Facility REVIEWER: Loren Makus ACTIVITY NUMBER: T05CM01574 SUMMARY: The Site Plan was reviewed by Development Services Department, Engineering Division on May 16, 2005. It was not approved. Please address the following comments. Site Plan Comments: 1. Clarify the extent and dimensions of the existing stockpile that is referenced on the plan. Also show existing contours and drainage patterns. (DS 2-02.2.1.A.23) 2. Show sight visibility triangles at Fairland Stravenue. Clarify the status of the existing street labeled as Old Vail Road. (DS 2-02.2.1.A.10) 3. Revise the Solid waste enclosure detail to provide steel posts along the sides. There must be 10 feet of clear space between the posts. (DS 2-02.2.1.A.32) 4. Show proposed drainage patterns, including roof drainage and finish grades. Show that sidewalks will be kept flood-free for up to a 10-year event. Show how that water harvesting will be maximized to the extent practicable. (DS 2-02.2.1.A.16) 5. Provide a drainage report discussing the retention requirements for this project. Include a discussion of the effects of the two different soil types on the project site. A grading permit is required for this project. Submit a complete grading permit application, including a drainage report and stormwater pollution prevention plan. Revise the Site Plan, to address all of these comments and resubmit two copies of each for review. Include a letter explaining how each comment has been addressed. Loren Makus, E.I.T. Senior Engineering Associate Engineering Division Development Services |
| 05/17/2005 | DAN CASTRO | ZONING HC SITE | REVIEW | Denied | Refer to Zoning Review comments regarding accessible ramp and path. |
| 05/17/2005 | DAN CASTRO | ZONING | REVIEW | Denied | COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. Scale on sheet 2 of 3 left hand corner is 1" = 40' and the actual scale as noted in the lower right corner of the sheet is 1" = 50'. Please revise. (D.S. 2-02.2.1.A.1) 2. List the legal description of the subject property. Per Pima County Assessors Records, the site is comprised of three (3) separate parcels which must be combined by providing a copy of the recorded City of Tucson Lot Combination Covenant. A copy of the City of Tucson Lot Combination Covenant is attached to the yellow site plan card or may be obtained online at www.ci.tucson.az.us/dsd/Lot_Combo_Declaration.pdf. (D.S. 2-02.2.1.A.2) (D.S. 2-02.2.1.A.2) 3. List the project address. (D.S. 2-02.2.1.A.3) 4. Provide the lot dimensions and bearings. 5. If lot split is proposed indicate as so on response letter. You may contact me at the number below for information regarding the lot split process. 6. The proposed height and square footage of all structures must be provided on the plan. Provide this information for the open sided shade structure called out on the plan. (D.S. 2-02.2.1.A.6) 7. Vehicle parking calculation is based on the proposed land use classification/s listed under LUC Sec. 3.3.4 Industrial Use Group. List the land use classification (i.e. General Manufacturing) to verify vehicle parking requirements. Vehicle parking is based on the gross floor area of the proposed building and the shade structure. Revise calculation as required. (D.S. 2-02.2.1.A.8) 8. Landing at top of ramp shall have a clear length of five (5) feet. ICC/ANSI A117.1-2003 Section 405.7.3. Where doorways are adjacent to a ramp landing, maneuvering clearances required by Sections 404.2.3 and 404.3.2shall be permitted to overlap the landing area. (D.S. 2-02.2.1.A.8) 9. Provide a fully dimensioned detail for the accessible ramp. Refer to section 405 of the ICC/ANSI A117.1-2003. (D.S. 2-02.2.1.A.8) 10. Provide the bicycle parking calculation. The number and class type required and provided shall be provided. Indicate the type of surface to be provided. The surface of an outdoor parking facility may be surfaced in the same manner as the motor vehicle parking area or with a minimum one (1) inch thickness of one-fourth (1/4) inch aggregate 11. Label and dimension sight visibility triangles at ingress/egress point/s. (D.S. 2-02.2.1.A.10) 12. Dimension width of all PAALs and ingress/egress point/s. (D.S. 2-02.2.1.A.11) 13. Dimension back-up spur. Minimum three (3) foot radii and depth required. (D.S. 3-05.2.2.D) 14. Indicate graphically or by note, the type of barrier (i.e. vertical curb, bollards, etc.) provided to prevent vehicle from encroaching onto unimproved portions of the site. 15. All vehicular use areas shall be surfaced with one (1) of the materials listed under LUC Sec. 3.3.7.3. 16. Clearly identify vehicular, pedestrian, and handicap circulation on the plan. An accessible pedestrian path shall be provided to new office building from the street frontage. Refer to D.S. 2-08 for on-site pedestrian circulation requirements. (D.S. 2-02.2.1.A.12) 17. If applicable, provide a fully dimensioned detail (location, type, size, and height) of existing and proposed free standing signage, billboard, and outdoor lighting on the site plan. (D.S. 2-02.2.1.A.13) (D.S. 2-02.2.1.A.25) 18. Per LUC Sec. 3.4.5.1 Industrial Use Group, the gross floor area of the proposed modular building and the shade structure require one (1) 12' x 55' loading space. Label and dimension the loading space on the plan and add a note which, states the number required and provided. (D.S. 2-02.2.1.A.14) (D.S. 2-02.2.2.A.5) 19. Dimension existing and future right-of-way and curb location for Fairland Stravenue on the plan. (D.S. 2-02.2.1.A.19) (D.S. 2-02.2.1.A.21) 20. If applicable, all existing and proposed easements must be shown on the plan including width, type, and recording docket and page reference. (D.S. 2-02.2.1.A.20) 21. Revise general note three (3) to state the proposed land use classification as it is listed under LUC Sec. 2.7.2.2.A. (land use classification, development designator, and applicable subject to section). 22. What is the correct site area? General note one (1) states 24.5 acres and the site data on the same sheet indicates 2.79 acres. Revise to be consistent or clarify the difference. 23. Provide the floor area ratio (FAR) calculation. (D.S. 2-02.2.2.A.3) 24. All requested changes must be made to the site and landscape plans. (D.S. 2-07.2.1.A) If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608 ext. 1180. An appointment is required to discuss these comments in person. |
| 05/20/2005 | ANDREW CONNOR | NPPO | REVIEW | Denied | Submit NPPO plan or application for exception per DS 2-15.0 |
| 05/20/2005 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | 1. Submit a separate landscape plan per DS 2-07.0. 2. Street landscape border is required. A street landscape border, Sec. 3.7.2.4 of the LUC, is a landscape area with a minimum width of ten (10) feet, running the full length of the street property line(s) bounding the site except for points of ingress-egress. 3. Fifty (50) percent or more of the street landscape border area must have shrubs and vegetative ground cover per LUC 3.7.2.4 4. 20% of shrubs in landscape border are required to be 5-gallon size DS 2-06.3.5. 5. One (1) canopy tree must be provided for every thirty-three (33) linear feet of landscape border per LUC 3.7.2.4 6. A 30" continuous screen along street frontages for vehicle use area must be provided. per LUC Table 3.7.2-I 7. Landscaping is required along retention basin side slopes, bottom and periphery. Plant materials used in basins shall withstand periodic inundation. A minimum of 20 trees per must be provided, 33% of tress shall be 24" box or larger. A minimum of (2) shrubs for each tree is required per DS 10.01. Additional planting for the basins is required. 8. Indicate square footage of all landscaped areas and calculation of the percentage of vegetative coverage per DS 2-07.2.2.2.g The planting plan and layout calculations will include the following Information: · Both the proper and common name of each type of plant material. · Locations, size, and name of all existing vegetation to remain in place. · Material and areas of inert ground cover. All disturbed areas including adjacent right of ways shall be treated with ground cover such as decomposed granite to help reduce dust pollution per LUC 3.7.2.7. Indicate treatment for landscaped areas. 9. Within vehicular use areas, one (1) canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.a 10. Landscaping along parking lots where plants are susceptible to injury by vehicular traffic must be protected by appropriate means, such as curbs, bollards, or low walls per LUC 3.7.2.3.B 11. The Vehicular use area must include post barricades or wheel stop curbing designed to prevent parked vehicles from extending beyond unpaved areas on or off site and to prevent vehicles from driving onto unimproved portions of the site. Provide barricades for all the vehicle use areas including access to other portions of the site per DS 3-05.2.3.C.1 12. Include irrigation system specifications, design, and layout per DS 2-06.5.4.A and 2-06.5.4.B. 13. Submit NPPO plan or application for exception per DS 2-15.0 14. Additional comments may apply |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/02/2005 | ANGIE SHOFFSTALL | OUT TO CUSTOMER | Completed |