Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T05CM01570
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/19/2007 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/19/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the quantity of outside air for AHU-3 to comply with the requirements of Section 403.3, IMC 2003. 2. Show that the revised airdistribution for the seating area served by AHU-1b will result in adequate distribution of the ventilation air. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/27/2007 | DELMA ROBEY | APPROVAL SHELF | Completed |
| 12/27/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 12/27/2007 | DELMA ROBEY | REJECT SHELF | Completed |