Permit Number: T05CM01570
Parcel: 12005275A

Address:
4654 S 16TH AV

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T05CM01570
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2007 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/19/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the quantity of outside air for AHU-3 to comply with the requirements of Section 403.3, IMC 2003.
2. Show that the revised airdistribution for the seating area served by AHU-1b will result in adequate distribution of the ventilation air.