Permit Number: T05CM01551
Parcel: 117050210

Address:
425 E 7TH ST

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01551
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2005 JIM EGAN FIRE REVIEW Approved
04/08/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
04/08/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
04/11/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/11/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1)CLARIFY / DETAIL CONNECTIONS FOR 3"X3"X1/4" ANGLE TO C-CHANNEL. PROVIDE STRUCTURAL CALCULATION. PROVIDE MODIFICATION DETAIL FOR HAINDRAILS / GUARDRAILS PER CODE 1009 AND 1012
2) RESTROOM FACILITIES ON FIRST FLOOR MEET ANSI A117.1 STANDARDS 2003 OR JUSTIFY PER CODE SECTION 3409.6. WITH A BRAKDOWN OF COSTS FOR THE ALTERATIONS.
3) PROVIDE SITE PLAN FOR ACCESSIBILTY INTO TENANT SPACE PER CHAPT. 11. SITE PLAN PROVIDED IS NOT CLEAR FOR RAMPS. CLARIFY LOCATION OF SLOPED RAMP.
04/11/2005 ROBERT SHERRY WATER REVIEW Approved
04/11/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/11/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations to show that the ventilation complies with the requirements of Section 403.3, IMC 2000.
04/18/2005 GBONILL1 WWM REVIEW Needs Review