Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01551
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/08/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
04/08/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
04/08/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
04/11/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
04/11/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1)CLARIFY / DETAIL CONNECTIONS FOR 3"X3"X1/4" ANGLE TO C-CHANNEL. PROVIDE STRUCTURAL CALCULATION. PROVIDE MODIFICATION DETAIL FOR HAINDRAILS / GUARDRAILS PER CODE 1009 AND 1012 2) RESTROOM FACILITIES ON FIRST FLOOR MEET ANSI A117.1 STANDARDS 2003 OR JUSTIFY PER CODE SECTION 3409.6. WITH A BRAKDOWN OF COSTS FOR THE ALTERATIONS. 3) PROVIDE SITE PLAN FOR ACCESSIBILTY INTO TENANT SPACE PER CHAPT. 11. SITE PLAN PROVIDED IS NOT CLEAR FOR RAMPS. CLARIFY LOCATION OF SLOPED RAMP. |
04/11/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/11/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/11/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide calculations to show that the ventilation complies with the requirements of Section 403.3, IMC 2000. |
04/18/2005 | GBONILL1 | WWM | REVIEW | Needs Review |