Parcel: 122160960

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T05CM01517
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2005 TERRY STEVENS ZONING REVIEW Approved
04/19/2005 GERRY KOZIOL WWM REVIEW Approved
05/16/2005 DAVE MANN BUILDING-RESIDENTIAL REVIEW Denied Sheet A-1
1. Patio wall footing looks like ti goes over property line.
Sheet A-2
1. Shower enclosres shall be finished per P2710 up to 72".
Sheet A-5
1. Building paper is required over wood sheathing.
Sheet A-6
1. Shower requires a plumbing vent.
2. Shower light to be listed for use.
3. Provide cut sheet and show how out door light will meet lighting code for light tresspass.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/17/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
05/17/2005 ANGIE SHOFFSTALL REJECT SHELF Completed