Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01499
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/05/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 04/05/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plumbing plan. 2. Provide descriptions of the proposed fixtures. |
| 04/05/2005 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/05/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show that the remodeled restroom meets the ventilation requirements of Section 403.3, IMC 2000. |
| 04/06/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 04/06/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 04/08/2005 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 04/08/2005 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 04/14/2005 | CAGUILA1 | WATER | REVIEW | Needs Review |