Permit Number: T05CM01497
Parcel: 140122170

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM01497
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/05/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide descriptions of the new hood, the new exhaust fan, and the balancing data.
2. Provide balancing data for the existing make-up air system.
04/05/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
04/05/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size to a minimum of 10 points.
2. Confirm the load for the existing water heater.
3. Show the total load for the meter and the developed pipe length used for the pipe sizing.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/05/2005 BETH GRANT OUT TO CUSTOMER Completed