Permit Number: T05CM01453
Parcel: 14027040B

Address:
2651 E GANLEY RD

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T05CM01453
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2005 ANDREW CONNOR LANDSCAPE REVIEW Approved
08/26/2005 DAN CASTRO ZONING HC SITE REVIEW Denied COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

This plan was reviewed for compliance with sections 2-02 of the Development Standards. Other sections of the Development Standard and Land Use Code are referenced as applicable.

1. Previous comment has not been addressed. Provide a detail showing compliance or add note as required.
Previous comment: Please provide a note on the plan showing all handicapped ramps will not exceed a slope ratio of 1:12.

2. Previous comment has not been addressed. Provide detail on the site plan showing compliance.
Previous comment: Truncated Domes (early warning systems) must be added to all access ramps where transitioning from the pedestrian area to the vehicular use area or at HC access aisles transitioning to the sidewalk area.

3. If you have any questions on this review, please contact me at Heather.Thrall@tucsonaz.gov or at 520-791-4541x1156 to make an office appointment.


If you have any questions about this transmittal, please call (520) 791-5608.
08/26/2005 DAN CASTRO ZONING REVIEW Denied COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

This plan was reviewed for compliance with sections 2-02 of the Development Standards. Other sections of the Development Standard and Land Use Code are referenced as applicable.

1. Previous comment has not been addressed. Provide a detail showing compliance or add note as required.
Previous comment: Please provide a note on the plan showing all handicapped ramps will not exceed a slope ratio of 1:12.

2. Previous comment has not been addressed. Provide detail on the site plan showing compliance.
Previous comment: Truncated Domes (early warning systems) must be added to all access ramps where transitioning from the pedestrian area to the vehicular use area or at HC access aisles transitioning to the sidewalk area.

3. If you have any questions on this review, please contact me at Heather.Thrall@tucsonaz.gov or at 520-791-4541x1156 to make an office appointment.


If you have any questions about this transmittal, please call (520) 791-5608.
09/19/2005 ELIZABETH EBERBACH ENGINEERING REVIEW Denied SUBJECT: 2651 E GANLEY RD Drainage Report and Site Review
LOCATION: T15S, R14E, Section 8
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: T05CM01453

Summary: Engineering Division has reviewed the resubmitted items, and may not recommend approval at this time. Please provide a revised site plan and a revised drainage report addressing the comments provided below. An over the counter review may be coordinated with me upon completion of these revisions.

DRAINAGE REPORT/SITE PLAN COMMENT:
1. DS 10-01: Per our meeting, the basin must be setback from any leachate field area - show setback on plan from ponding limits / basin area. Regarding basin access, pedestrian or vehicle access for maintenance maybe located at human activity zone (project amenity, a multi-use facility, passive recreation) access.

I can be reached at 791-5550, ext.2204 if you have questions.

Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services Department