Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM01453
Parcel: 14027040B

Address:
2651 E GANLEY RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM01453
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Lighting Power Budget calculations per the 2000 IECC shall be based on 0.6 W/SF. Reference Table 805.4.2, Industrial/Commercial Storage.
2. Fault calculations, appear to use incorrect impedance values. Reference our conversation of January 5, 2006.
3. Please note that the Owner may not occupy this building if it is to be considered as a shell. This is not an electrical issue, but needs to be clarified among the Building Plans Examiner, Architect, and Owner.
12/21/2005 SEPTIC APPROVAL WWM REVIEW Needs Review septic has not been reviewed yet.
12/21/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approv-Cond
12/21/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/21/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 4. The water calculations show a developed pipe length of 297 feet but drawing P-1.0 shows a developed pipe length of approximately 264 feet from the SOV to the furthest outlet. In addition, Keynote 19 (sheet C-1.0) calls out 179 feet of pipe from the water meter to within five feet of the building. Recalculate the equivalent pipe length and the permissible friction loss. Revise pipe sizes as required. Reference Section A3, UPC 1994.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/10/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
01/10/2006 SUE REEVES REJECT SHELF Completed