Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T05CM01449
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/31/2005 | NEAL SAUNDERS | BUILDING-RESIDENTIAL | REVIEW | Approved | |
| 03/31/2005 | GERRY KOZIOL | WWM | REVIEW | Passed |