Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM01408
Parcel: 11202035A

Review Status: Completed

Review Details: REVISION

Permit Number - T05CM01408
Review Name: REVISION
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/19/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Eliminate redundant 1/0 Ground in conduit runs between TEP Transformer and Terminal Cabinet, between Terminal Cabinet and CT enclosure, and between CT enclosure and service disconnect enclosure. Size Grounding Electrode Conductor to Grounding Electrode: 1/0.
2. Change the wording "New Trailer" to read "Future Trailer." Otherwise the trailer itself has to be approved by the State Board of Manufactured Housing, and the feeder, disconnect, and grounding electrode system for the new trailer has to be indicated on the plans, along with its inclusion on the site plan.
3. On Sheet E8, please change the wording "NEC 230.3 (E)" to read "NEC 230.2 (E)."
4. Indicate fault current rating for new 480V service equipment. With TEP's AFC of 32,600 A at its secondary, aprox. 225' to the new service, and (2) paralled 500 MCM for a "c" value of 26706, it appears that the ACF at the service is less than 22KA.
5. Please change the conduit size in the run from the CT can to the new service equipment from 1" to 3" for the (4) 350 MCM.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/26/2005 SUE REEVES APPROVAL SHELF Completed
09/26/2005 GBONILL1 OUT TO CUSTOMER Completed