Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01408
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/31/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
04/01/2005 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/18/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
04/19/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. If the humidifier for FC-1 is to be directly connected to the water supply system and does not have a listed, integral backflow preventer or an integral air gap, it may require a reduced pressure principle backflow preventer. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994. |
04/19/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/19/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show that the smoke detector for FC-1 is located upstream of any outside air connections. Reference Section 606.2.1, IMC 2000. 2. Coordinate the capacity of the maximum overcurrent protective device called for by the manufacturer of FC-1 with the submitted electrical design. Reference Section 304.1, IMC 2000. |
05/04/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approv-Cond |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/13/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
05/13/2005 | SUE REEVES | REJECT SHELF | Completed |