Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM01408
Parcel: 11202035A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01408
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/31/2005 JIM EGAN FIRE REVIEW Approved
04/01/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
04/18/2005 GERRY KOZIOL WWM REVIEW Approved
04/19/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. If the humidifier for FC-1 is to be directly connected to the water supply system and does not have a listed, integral backflow preventer or an integral air gap, it may require a reduced pressure principle backflow preventer. Please submit equipment sheets for determination. Reference Section 603.0, UPC 1994.
04/19/2005 ROBERT SHERRY WATER REVIEW Approved
04/19/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show that the smoke detector for FC-1 is located upstream of any outside air connections. Reference Section 606.2.1, IMC 2000.
2. Coordinate the capacity of the maximum overcurrent protective device called for by the manufacturer of FC-1 with the submitted electrical design. Reference Section 304.1, IMC 2000.
05/04/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approv-Cond

Final Status

Task End Date Reviewer's Name Type of Review Description
05/13/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
05/13/2005 SUE REEVES REJECT SHELF Completed