Permit Number: T05CM01334
Parcel: 128100530

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM01334
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/25/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/25/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide a description of the ice machine noted on detail 2/P-2. If it is to be directly connected to the water piping, provide backflow protection. Reference Section 103.2.3, UPC 1994.
2. Indirect waste receptors shall be installed in readily accessible locations (see floor plan, sheet P-1). Coordinate the location of the floor sink with architectural sheet A-1. Reference Section 804.1, UPC 1994.
04/25/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/26/2005 DELMA ROBEY OUT TO CUSTOMER Completed