Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM01334
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/25/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/25/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Provide a description of the ice machine noted on detail 2/P-2. If it is to be directly connected to the water piping, provide backflow protection. Reference Section 103.2.3, UPC 1994. 2. Indirect waste receptors shall be installed in readily accessible locations (see floor plan, sheet P-1). Coordinate the location of the floor sink with architectural sheet A-1. Reference Section 804.1, UPC 1994. |
| 04/25/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/26/2005 | DELMA ROBEY | OUT TO CUSTOMER | Completed |