Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2005 GERRY KOZIOL WWM REVIEW Approved
03/30/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
04/07/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Indicate the type of water closet being installed (i.e. tank or flushvalve). Revise the water pipe sizes if required.
04/07/2005 ROBERT SHERRY WATER REVIEW Approved
04/07/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Terminate condensate drains in accordance with Section 307.2.1, IMC as amended by the City of Tucson. Termination at the tailpipe of a sink (as opposed to a lavatory) is not allowed.
2. Show how the relocated fan coil is supported from the structure. Reference Section 106.3.1, IMC 2000.
3. Show that the duct liner meets the requirements of Section 803.2.8, IECC 2000.
4. Clarify if the project area has a return air plenum and if it does, show that the materials in the plenum conform with the requirements of Section 602.2, IMC 2000 and that smoke detectors have been installed per Section 606.2.2, IMC 2000.
5. Show what is being done with the chilled and heating water pipes (general note #3 and keynotes # 3 & 11, Sheet M-1) and that they are sized to meet the system demand. Reference Section 1201.2, IMC 2000.
6. Clarify that the insulation for the chilled water piping meets the requirements of Section 803.3.7, IECC 2000 by having a conductivity not exceeding 0.27 BTUH/inch/Ft^2 /°F.
7. Revise the insulation for the heating water piping to meet the requirements of Section 803.3.7, IECC 2000.
8. Clarify how the sequence of operation for the restroom exhaust fan will prevent recirculation of the air from the restroom. Reference Section 403.2.1 and Footnote (b) of Table 403.3, IMC 2000.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/11/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
04/11/2005 CINDY AGUILAR REJECT SHELF Completed