Permit Number: T05CM01287
Parcel: 13623007Y

Address:
2712 S KOLB RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01287
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2005 JIM EGAN FIRE REVIEW Approved
03/24/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the location of the hot water return pipe on the riser diagram.
2. Provide information to show how the RPBP's are being installed and that this installatin meets the listing requirements for the valve. Show that adequate service space is available for the valves.
03/24/2005 PETER MCLAUGHLIN ZONING REVIEW Approved
03/24/2005 ROBERT SHERRY WATER REVIEW Approved
03/24/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
03/24/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/25/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
04/04/2005 CAGUILA1 WWM REVIEW Needs Review
04/04/2005 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review