Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01286
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/23/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 03/23/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/23/2005 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 03/23/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 03/24/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show that the existing 1" water pipe will not be overloaded with the addition of the new fixtures. Include the head losses (e.g. meter, RPBP losses, lift) when determining the available static pressure for use in Table 6-4. 2. Provide the size of the waste line from the lav to show that the waste line from P1 can be accommodated. 3. Provide a description of P2 and show the size of the proposed waste line. 4. Show how the water heater is mounted. 5. The water heater detail calls for a drain line to be routed to a service sink or a floor sink. Show the route and termination of the drain line on the plans. 6. The minimum trap size for a clotheswasher is 2". |
| 03/24/2005 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/24/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 03/24/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Verify the exhaust volume for the restroom complies with the requirements of Section 403.3, IMC 2000. Provide a sequence of operation for the fan to show that there will be no recirculation of the supply air from the restroom. |
| 04/05/2005 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/05/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |