Permit Number: T05CM01250
Parcel: 116122870

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM01250
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2005 ROBERT SHERRY WATER REVIEW Approved
05/17/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify how the specified air filters will filter the outside air.
2. The minimum exhaust flow rate for commercial restrooms is 75 CFM per water closet.
3. Recirculation of the air supplied to a restroom is not allowed. Show how this will be accomplished. Reference Section 403.2, IMC 2000.
05/17/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Correct the arithmetic for the pressure loss calculations.
2. Revise the arrangement of the backflow preventer for the main water supply (the RPBP is to be located after the water meter).
05/19/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved t05cm01250 DENIED 5/17/05

The #6 in the conduit between the Main Disconnect Panel A and the meter is a redundant path to ground. Please remove. Reference NEC 250.28.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/19/2005 KMEDINA1 OUT TO CUSTOMER Completed