| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/17/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/17/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify how the specified air filters will filter the outside air. 2. The minimum exhaust flow rate for commercial restrooms is 75 CFM per water closet. 3. Recirculation of the air supplied to a restroom is not allowed. Show how this will be accomplished. Reference Section 403.2, IMC 2000. |
| 05/17/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Correct the arithmetic for the pressure loss calculations. 2. Revise the arrangement of the backflow preventer for the main water supply (the RPBP is to be located after the water meter). |
| 05/19/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | t05cm01250 DENIED 5/17/05 The #6 in the conduit between the Main Disconnect Panel A and the meter is a redundant path to ground. Please remove. Reference NEC 250.28. |