Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM01250
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/10/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 05/10/2005 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | |
| 05/10/2005 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 05/11/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the water riser diagrams to include the water heater. 2. Show how the water pipes entering and leaving the water heater are insulated. Reference Section 804, IECC 2000. 3. Show all of the existing fixtures being re-piped. 4. Show the location and size of the reduced pressure backflow preventer for the office area. |
| 05/11/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 05/11/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/11/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM01250 DENIED 5/11/05 1. Demonstrate compliance with the Lighting Ordinance. http://www.ci.tucson.az.us/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf. 2. Provide available fault current at the service. 3. Provide fault current ratings of new equipment. 4. Provide fault calculations as necessary to demonstrate that all equipment is rated for AFC. 5. According to the Lighting Fixture Schedule, load is 150 VA per lighting fixture. This would be (6) (150) (1.25) = 1125 VA for lighting load on the Electrical Load Summary, not 245 VA. 6. Add 25% for the largest motor load on the Panel A Load Summary. 7. Specify the feeder size for Panel A. 8. Demonstrate that the existing electrical service was overhead, or specify an underground service. |
| 05/11/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the size, route, and termination of the condensate drains from the heat pumps. 2. Specify the insulation for the ductwork. Reference Section 803.2.8, IECC 2000. 3. Specify the location and efficiency of the air filters for the heat pumps. |
| 05/17/2005 | GERRY KOZIOL | WWM | REVIEW | Approved |