Permit Number: T05CM01250
Parcel: 116122870

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM01250
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2005 JIM EGAN FIRE REVIEW Approved
05/10/2005 PETER MCLAUGHLIN ZONING REVIEW Approved
05/10/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
05/11/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the water riser diagrams to include the water heater.
2. Show how the water pipes entering and leaving the water heater are insulated. Reference Section 804, IECC 2000.
3. Show all of the existing fixtures being re-piped.
4. Show the location and size of the reduced pressure backflow preventer for the office area.
05/11/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
05/11/2005 ROBERT SHERRY WATER REVIEW Approved
05/11/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM01250 DENIED 5/11/05

1. Demonstrate compliance with the Lighting Ordinance. http://www.ci.tucson.az.us/dsd/Codes___Ordinances/Tucson_Lighting_Code.pdf.
2. Provide available fault current at the service.
3. Provide fault current ratings of new equipment.
4. Provide fault calculations as necessary to demonstrate that all equipment is rated for AFC.
5. According to the Lighting Fixture Schedule, load is 150 VA per lighting fixture. This would be (6) (150) (1.25) = 1125 VA for lighting load on the Electrical Load Summary, not 245 VA.
6. Add 25% for the largest motor load on the Panel A Load Summary.
7. Specify the feeder size for Panel A.
8. Demonstrate that the existing electrical service was overhead, or specify an underground service.
05/11/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the size, route, and termination of the condensate drains from the heat pumps.
2. Specify the insulation for the ductwork. Reference Section 803.2.8, IECC 2000.
3. Specify the location and efficiency of the air filters for the heat pumps.
05/17/2005 GERRY KOZIOL WWM REVIEW Approved