Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM01144
Parcel: 10604098C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM01144
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2005 GERRY KOZIOL WWM REVIEW Approved
11/29/2005 JIM EGAN FIRE REVIEW Approved
12/02/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The revised drawings do provide upper terminal cleanouts however Section 707.11 requires that the cleanouts "not be less in size than that given in Table 7-6." As a result, each change in pipe size that results in a change in the cleanout size will require an additional cleanout of the proper size. The section of 3" building drain located between the connection of the lavatory and the water closet in the South apartment requires a 2-1/2" cleanout as does the section of 3" building drain located between the tub and the water closet in the North apartment. (Note that changing those sections to 2" pipe will resolve the problem.)
2. The provided water supply isometric displays two problems: some of the pipe sizes are too small based on your calculations (after correcting the arithmetic, the allowable friction loss is 8.8 PSI / 100 feet) and the termination of the hot and cold water piping does not conform to Section 601.2, UPC 1994.
12/02/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 10/7/05
ACTIVITY NUMBER: T05CM01144
PROJECT NAME: Storage Bldg. Converted to 3 residential units
PROJECT ADDRESS: 340 E. Yavapai Rd.
ARCHITECT / ENGINEER: BT design group
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Clarify location of overhang from property line. See section 704.2.3 It appears underside of overhang and facia will need to be fire rated. Your argument is only good at the location of wall, once the projection proceeds past the wall it must be fire rated. Per your request I referred your response to Dave Mann and his interpretation agrees with as I stated above.

2) Permit will not be approved until zoning has approved site plan.
12/02/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/14/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved Building Only
12/15/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide Arc-fault circuit protection as required in NEC 210.12, for all branch circuits powering bedroom 125V single-phase 15A and 20A outlets. This includes lighting fixtures. See NEC Handbook, commentary to 210.12 for clarification.
12/22/2005 PETER MCLAUGHLIN ZONING REVIEW Denied Zoning has reviewed the building plans but cannot approve them at this time. Zoning will re-review and approve the building plans on the next submittal providing the stamped and approved site plans are included with the building plan package.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/09/2006 GBONILL1 OUT TO CUSTOMER Completed
01/09/2006 SUE REEVES REJECT SHELF Completed